KM 410 IAQ Wöhler

Po naročilu. Pošljite povpraševanje.
Delivery time: approximately 2-3 weeks
- CO2measurement( NDIRsensor ): 0 … 5.000 ppm
- measurement CO: 0 … 1.000 ppm
temperature:
-20 . ..60 °C- relative humidity air humidity: 0.1 … 99.9 % r. H.
[Sassy_Social_Share]
Description
The KM 410 IAQ Wöhler is an air qualitymeter for indoor space. Odlichen instrument For check operation system
HVAC
and ventilationcontrol.
Main features
- Precise measurement of SO₂ – NDIR (non-dispersive infrared absorption) process
- measurement report – with a high-speed thermal printer Wöhler TD 100
- All IAQ values – in one device
- Additional CO sensor
- data logger
- Blue rear light – for use in dark areas
- alarm function – acoustic and visual
- hold function – freezes the current reading
- maximum/minimum values
Technical data
CO2 measurement( NDIRsensor )
- the measuring area: 0 … 5.000 ppm
- resolution: 1 ppm
- accuracy: ±30 ppm ±5 %
- Phase heating: 30 s
- Responsive time: <30 s
Measurement CO
- measuring range: 0 … 1.000 ppm
- resolution: 1 ppm
- accuracy:
- ±10 ppm or less as 100 ppm
- ±10 % between 101 … 500 ppm
- ±20 % Read more than 501 ppm
- ±10 ppm or less as 100 ppm
- Responsive time: <60 s
Temperature
- measuring range:-20 … 60 °C
- resolution: 0.1 °C
- accuracy: ±0.5 °C
Relative humidity air
- measuring range: 0.1 … 99.9 % r. H.
- resolution: 0.1 % r. H.
- accuracy:
- ±3 % at 10 … 90 % r. H. in 25 °C
- ±5 % r. H. at other measurements and 25 °C
- ±3 % at 10 … 90 % r. H. in 25 °C
- Responsive time: <10 s
Main technical features
- Working temperature: 0 … 50 °C
- storage temperature : 20 .. .60°C, 10 … 90 % r. h . , non-condensing
- power supply: s 4 batteries AA or Network power supply z 9 V-DC adapter(not included)
- PC: interface USB
- memory: 6.000 per list of CO2, temp. , r. H. , CO
- lograti: 1 s … 4 h 49m 59s
- dimensions: 205 x 70 x 56 mm
- weight: 200 g
Software and driver
Use
The meter checks the operation of the HVAC system and ventilation control. Measures CO2 levels, air temperature and relative humidity. It also determines the CO the dew point and wet bulb temperature.
Other designations: 4280, KM_410 IAQ, KM410IAQ